Australian (SAA) Certified (DL2, DL3) 4V-75 Polyvinyl Chloride (PVC) Flexible Cable (with

The technical requirements, test methods and inspection rules of the wire are referred to below.

Rated voltage 250/440V, 0.6/1KV, operating temperature 75°C, two- and three-core polychlorinated

Ethylene insulation, PVC sheathed soft power cord factory inspection basis.


The clauses in the following documents have been adopted as references to this standard. All dated references, which

All subsequent amendments (not including errata content) or revisions do not apply to this standard, however, encourage compliance with this standard.

The parties to the agreement study whether the latest versions of these documents can be used. For undated references, the latest version is suitable.

Used for this standard.

GB/T 2951.1 General Test Method for Cable Insulation and Sheath Materials

Part 1 General Test Methods Section 1 Thickness and Dimensional Measurements - Mechanical Properties Tests

VDE0281.2 rated voltage 450/750 and plug with pvc power cord


Part II: Test Methods 3 Technical Requirements and Test Methods

Inspection and test according to delivery status

3.1 Basic Parameters and Structure Size

The basic parameters and dimensions of the wire should meet the requirements of Table 1 and Table 2.


Model Number (reference) mm

Number of cores and conductors

Nominal cross

Cross section mm2 Nominal thinnest point Lower limit Upper limit

At 20°C

Conductor resistance

Ω/km

Insulation at 70°C

Resistance minimum

MΩ·km

DL2 4V-75 2×0.5 3.0×4.9 3.7×5.9 39.0 0.012

250/440V 2×075

0.5 0.35 0.6 0.41

3.2 x 5.2 3.8 x 6.3 26.0 0.010

2×0.75 5.7 7.2 26.0 0.011

2×1.0

0.6 0.44 0.8 0.58

5.9 7.5 19.5 0.010

2×1.5 0.7 0.53 0.8 0.58 6.8 8.6 13.3 0.010

2×2.5 0.8 0.62 1.0 0.75 8.4 10.6 7.98 0.009

3×0.75 6.0 7.6 26.0 0.011

3×1.0

0.6 0.44 0.8 0.58

6.3 8.0 19.5 0.010

3×1.5 0.7 0.53 0.9 0.67 7.4 9.4 13.3 0.010

DL2, DL3

4V-75

250/440V

3 x 2.5 0.8 0.62 0.11 0.84 9.2 11.4 7.98 0.009


Model Number (reference) mm

Number of cores and conductors

Nominal cross

Cross section mm2 Nominal thinnest point Lower limit Upper limit

At 20°C

Conductor resistance

Ω/km

Insulation at 70°C

Resistance minimum

MΩ·km

2×0.75 7.5 9.0 26.0 0.011

2×1.0

1.3 1.01

7.7 9.2 19.5 0.010

2×1.5

0.8 0.62

1.5 1.18 8.7 10.2 13.3 0.010

3×1.0 1.4 1.09 8.4 10 19.5 0.010

3×1.5

0.8 0.62

1.6 1.26 9.3 11.0 13.3 0.010

DL2, DL3

4V-75

0.6/1KV

3 x 2.5 0.9 0.71 1.8 1.43 11 13.0 7.98 0.009


Ellipticity: The diameter of any two outer diameters measured on the same cross-section of a round sheathed wire shall not exceed the average outer diameter gauge

15% of the upper limit.

Whether it is qualified or not, measure according to Article 8 of GB/T 2 95.1.

3.2 Conductor resistance

Conductor resistance should meet the requirements of Table 1~2.

Compliance with Article 2.1 of the VDE 0281.2 standard.

3.3 Finished wire withstand voltage test

The finished wire and cable shall be subjected to the immersion voltage test specified in Table 3 without breakdown.

Compliance is checked by the provisions of section 2.2 of the VDE 0281.2 standard.

3.4 Insulated core withstand voltage test

The sheath and other sheaths or cores should be stripped first, placed in the water bath specified in Table 3, and applied between the conductor and the water

Pressure without breakdown.


Finished cable, insulated core withstand voltage test

sequence

number

Test requirement

Cable rated voltage

250/250V and 250/440V

Cable rated voltage

0.6/1KV

Sample length min m 20 20

Water immersion time at least h 1 1

Water temperature °C 20±5 20±5

Test voltage V 2000 2500

1

Finished product

Cable voltage

test

Voltage application time min 15 15

Sample length min m 5 5

Water immersion time at least h 1 1

Water temperature °C 20±5 20±5

Test insulation wall thickness ≤0.6 mm V 1500 ——

Voltage Insulation Wall Thickness >0.6 mm V 2000 2500

2

The finished product must

Edge core

Voltage test

Test

Voltage application time min 5 5


3.5 Insulation resistance

The insulation resistance of the cable should meet the requirements of Table 1~2.

Compliance is checked by the provisions of 2.4 of VDE 0281.2.

3.6 Logo

Wire and cable signs should be correct, the content of the mark: model, specifications, manufacturers (marked when the record for certification) and certification mark

Zhi, such as "N16066". The writing is clear and easy to identify.

The distance between the end of one complete mark and the beginning of the next mark, the sheath should not exceed 550mm.

The logo can be printed with ink, or it can be imprinted on the insulation or sheath with a male or female die.

The ink printing mark is to be tested for rub resistance. During the test, gently wipe it 10 times with a piece of soaked absorbent cotton or a piece of cotton cloth.

After that, the handwriting should still be legible.

Compliance is checked by means of visual inspection; signs are measured continuously with a ruler; signs are rubbed in accordance with 1.8 in VDE 0281.2

Definite test inspection.


4 Inspection Rules

4.1 Sampling

In each batch of factory wire and cable randomly selected, each 20km extraction were randomly tested, only after passing the factory.

4.2 Procedures

The inspection items shall be carried out item by item according to item 3.1~3.6 of this standard.

4.3 Passing judgment

After the factory inspection, if there is any unqualified product, the number of unqualified items will double, and if it is still unqualified,

The batch of power lines was judged as unqualified.